Pitot Tube Flow Meter

AUD $3,502AUD $4,530

Pitot Tube flow meter. Ideally suited to wet, dirty and high velocity compressed air and inert gas systems that contain some level of contamination.

Flow Range
5 – 300 Nm/s (17 to 984 ft/s)

Gas Pressure Range
up to 17 bar (247 psi)

Gas Quality
Wet, dirty and high velocity compressed air and inert gas systems

Pipe Sizes
DN25 to DN600

Accuracy
Flow: ±1.5% reading, ±0.3% full scale
Pressure: ±0.5% full scale

Output
Modbus (RS485) and 4-20mA

Measure
Flow, Consumption, Pressure, Temperature

Power Requirement
18 to 30VDC / 6.5W@24VDC

Bi-directional
Optional

Measurement Principal
Volumetric

Application
Manufacturing and industrial use
Temporary or permanent installation

Accessories
Our Flow Meters have BSP thread. If your fittings are NPT thread, you will need a BSP to NPT adapter
The transparent Flow Meter Enclosure will protect the flow meter head from liquids and other damage
Extra M12 connectors and data cables are available on the Accessories page

Australian dollar ($) - AUD
  • Australian dollar ($) - AUD
  • United States dollar ($) - USD
  • Euro (€) - EUR
  • Canadian dollar ($) - CAD
  • Pound sterling (£) - GBP
  • Singapore dollar ($) - SGD

Pitot tube flow meters are ideally suited to wet, dirty and high velocity compressed air and gas systems that contain some level of contamination. This makes a pitot tube flow meter ideal for measuring flow, temperature and pressure near the outlet of compressors and other difficult environments.

Pitot tube flow meters have no moving parts, a low pressure drop and are vibration proof. The integrated pressure and temperature sensors give real-time monitoring of fluid pressure and temperature. The sensor has an extremely sensitive differential pressure measurement that allows pitot tube flow meters to be used over a wide flow range, whilst the patented anti-condensation technology ensures the sensor can be used under 100% saturated conditions. The flow meter can be easily installed under pressure through a 1/2″ ball valve.

Innovative online auto-calibration technology compensates for temperature and pressure changes, enabling the pitot tube flow meter to perform stable accurate measurements for years to come.

Best suited to

  • Wet and dirty gases
  • High velocity gases (5 to 300 Nm/s or 17 to 984 ft/s)
    • Note: below minimum velocity flow, the meter read will be zero. If your gas flow rate is less than 5 Nm/s (17 ft/s) and your gas is clean and dry, we recommend a Thermal Mass Flow Sensor.
  • Permanent or temporary installation

Features of Pitot Tube Flow Meters

  • Insertion type sensor
  • Ideal for wet and dirty gases
  • Flow range of 5 – 300 Nm/s (17 to 984 ft/s)
    • Note: below minimum velocity flow, the meter read will be zero. If your gas flow rate is less than 5 Nm/s (17 ft/s) and your gas is clean and dry, we recommend a Thermal Mass Flow Sensor.
  • Accuracy of +/-1.5% reading, +/-0.3% full scale
  • Integrated display with touch panel and data logging
  • Two output types as standard:
    • Digital – Modbus RTU and
    • Analog – 4-20 mA + Pulse
  • Suitable for pipes from DN25-DN600 provided minimum velocity (min 5 Nm/s or 17 ft/s) is maintained
  • Easy to insert and remove through 1/2″ valve, even when under pressure
  • ISO G1/2″ screw connection
  • Full electrical isolation to filter out disturbances
  • No moving parts, low pressure drop
  • Stable signals, vibration resistant
  • Extremely sensitive differential pressure sensor
  • Integrated pressure and temperature sensors for real-time monitoring of fluid pressure and temperature
  • Innovative online auto-calibration function to compensate the temperature and pressure change
  • Patented anti condensation technology
  • Anti-particulate pollution, oil vapour and most chemicals

Important

  • You need to maintain a minimum flow velocity of 5 Nm/s (17 ft/s) for the pitot tube to work correctly. Below this minimum velocity, the flow meter reading will be zero.
  • Flow meters must be installed away from bends, edges, seams, changes in pipe size and other obstructions
  • Incorrect wiring or installation can give false readings, damage the sensor and void the warranty. If you aren’t sure how to install or wire the sensor, please contact us. Full installation and wiring instructions are available in the User Manual.

Pitot Tube Flow Meter comes with:

  • M12 connector (data cable optional)
  • Calibration certificate
  • User Manual
  • 12 month warranty

Pitot Tube Flow Meter Options

  • Two shaft length options: 250 mm (9.8″) or 400 mm (15.7″)
  • Multiple gas options: Air, Argon, Carbon Dioxide, Helium, Hydrogen, Natural Gas, Nitrogen, Nitrous Oxide and Oxygen

Warranty & Calibration

12 month warranty

Calibration is recommended every 2 years (provided the sensor is not exposed to relative humidity above 85%).
Annual calibration is required if the sensor is exposed to relative humidity above 85%.

Technical Documents

User Manual

Quick Installation Guide (refer to User Manual for full installation instructions)

Product Flyer

Accessories

Accessories such as mechanical and electrical fittings are available on the Accessories page.

Other Information

Part Numbers: FLP100001, FLP200001, FLP110001, FLP210001, FLP110011, FLP210011

Please refer to our Terms and Conditions of Sale.

 

Weight 2.5 kg
Dimensions 69.5 × 21 × 17 cm

Specifications

General

Technology

Anti-condensation

Gases

Air, Argon, Carbon Dioxide, Helium, Hydrogen, Natural Gas, Nitrogen, Nitrous Oxide, Oxygen

Gas Quality

  • Wet and dry air
  • High velocity

Accuracy

Flow: ±(1.5% reading + 0.3% full scale)

Pressure: ±0.5% full scale

Temperature: ±0.5°C

Note: the accuracy of the sensor is affected by on-site conditions. Contaminants such as oil, high humidity or other impurities can affect the calibration and accuracy of the sensor.

Minimum Gas Flow Required

  • > 5 Nm/s
  • > 17 ft/s

Note: below this the Pitot Tube Flow Meter will read zero (“0”)

Measurement Ranges

Flow Measurement Range

  • 5 – 300 Nm/s
  • 17 to 984 ft/s

Pressure Measurement Range

  • 0 to 17 bar (17MPa)
  • 0 to 247 psi

Gas Temperature Measurement Range

  • -40°C to +150°C
  • -40°F to +302°F

Output

Outputs

  • Analogue: 4 to 20mA (3 wire)
  • Digital: RS485 Modbus / RTU

Modbus Output Signals

  • Flow
  • Consumption
  • Pressure
  • Temperature

Analogue Output Signals

One measurement only

Power Supply

Power

  • Power Supply: 18 to 30VDC / 6.5W@24VDC
  • Anti Condensate Power Up: 18 to 30VDC / 24W@24VDC

Electrical Connection

2 x 5 pin M12, female

EMC

According to IEC 61326-1

Data Logger and Display

Data Logger

10,000,000 samples

> 20 samples / second

Display

2.8” LCD with touch panel

Other Information

Pipe Sizes

DN25 to DN300

Shaft Length

  • 250 mm or 400 mm
  • 9.8” or 15.7”

Process Connection

ISO G1/2″ thread

Ambient Temperature Range

  • -20°C to +60°C
  • -4°F to +140°F

Installation Type

  • Permanent installation, or
  • Temporary installation

Calibration Frequency

  • Every 2 years (provided the sensor is not exposed to relative humidity above 85%).
  • Annual calibration is required if the sensor is exposed to relative humidity above 85%.

Warranty Period

12 months

Downloads

Installation Manual

Quick Install Guide

Product Flyer

Pitot Tube Flow Meter - User Manual Cover Pitot Tube Flow Meter Quick Guide Pitot Tube Flow Meter - Flyer Cover Page