Menu Close

Power Meter – Panel Mount with Display

USD $589USD $667

This single or three-phase, panel mount power meter is ideal for installation on main or sub-distribution boards where readings need to be accessed without opening the panel.

Type
3 phase multi-function power meter

Mounting
Panel Mount

Measured Voltage and Frequency
100V to 500V, 50/60Hz

Output
Modbus RS485

Measurements
Voltage, amps, frequency, kilowatts, kilowatt hours, power factor, real power, reactive power, apparent power and harmonics

Accuracy
±2%

Display
3.5 Inch TFT screen display

Rogowski Coils options
Comes with 3 rogowski coils
Options: 500 amps, 1,000 amps or 3,000 amps

Power requirement
85 to 265 V AC/DC, 3.5W

Application
Manufacturing and industrial use
Temporary or permanent installation
Mains supply and sub metering individual equipment or sub loads

United States dollar ($) - USD
  • Australian dollar ($) - AUD
  • United States dollar ($) - USD
  • Euro (€) - EUR
  • Canadian dollar ($) - CAD
  • Pound sterling (£) - GBP
  • Singapore dollar ($) - SGD
SKU: POM300 Categories: , Tag:

This single or three-phase, panel mount power meter is ideal for installation on main or sub-distribution boards where readings need to be accessed without opening the panel. The Modbus RTU output can be connected to your data acquisition system for easy access to data remotely.

Monitoring power consumption will give you a clear indication of the energy and cost of running your compressed air system. This power meter measures Voltage, Amps, Frequency, Kilowatts, Power factor, Real Power, Reactive Power, Apparent Power, Kilowatt hours and harmonics. It can be installed on mains supply or used for sub metering individual equipment or sub loads.

Installing a panel mount power meter is not difficult but should be done by suitably qualified and experienced technicians. Some knowledge of MODBUS communications is required to connect the power meters to your network

The unit comes with 3 rogowski coils current transducers. Rogowski coils have a large flexible coil and are an excellent solution where a traditional current clamp is too difficult to fit. The coil is shielded against the influence of external magnetic fields and is suitable for high power load analysis. Coils can be fastened by cable ties for permanent installs.

Best suited to

  • 3 phase or single phase measurements
  • Permanent installations
  • Panel mounting

Key features of the Panel Mount Power Meter

  • Multi-function meter with display
  • Measure single or three phase power with the same meter
  • Panel mount
  • Modbus/RTU output
  • Easy to install rogowski coil current transducers
  • Measure: Voltage, Amps, Frequency, Kilowatts, Power factor, Real Power, Reactive Power, Apparent Power, Kilowatt hours and Harmonics
  • 3 rogowski coil current rating options
  • Can be installed on mains supply
  • Can be used for sub metering individual equipment or sub load
  • 12 month warranty

Options for the Panel Mount Power Meter

  • Rogowski Coil current rating – 500 amps, 1,000 amps or 3,000 amps

Contact us for other Rogowski Coil sizes.

Warranty

12 month warranty

Technical Documents

User Manual

Other Information

Part Numbers: POM300100, POM300200, POM300300

Please refer to our Terms and Conditions of Sale.

Weight N/A
Dimensions N/A

Specifications

General

Type

Multi-function power meter suitable for power analysis, energy metering and tariff meter

Mounting

Panel Mount

Poles Description

  • 3PH4W
  • 3PH3W
  • 1PH2W (L-N)
  • 1PH2W (L-L)
  • 1PH3W (L-L-N)

Display

3.5 Inch TFT screen display

Accuracy

±2%

Note: the accuracy of the sensor is affected by installation location and on-site conditions.

Measured Voltage and Frequency

  • 100V to 500V
  • 50/60Hz

Sampling Rate

8,000 samples per second

Harmonic

52th Max

Outputs

Output

Digital: RS485 Modbus / RTU

Output Signals

  • Voltage for each phase
  • Amps for each phase
  • Kilowatts for each phase
  • Power factor
  • Reactive Power (kVa)
  • Total Kilowatts
  • Kilowatt hours
  • Electrical system harmonics

Inputs

Input Type

  • External CT (333mV only) or
  • External Rogowski coil

Primary current range

Adjustable from 0.1A to 9999A

Measurement Input range

1/2 ^25mV to 333mV

Permissible overload

600mV for 10s/hours

Power Supply

Power Supply

  • 85 to 265 V AC/DC, 3.5W

Electrical Connection

Terminal strip

Other Information

Alarm

  • Relay
  • Voltage and current, each phase, average all phases

Dimensions

  • 96 mm L x 96 mm W x 99 mm D
  • 3.8” L x 3.8” W x 3.9” D

Ambient Temperature Rang

  • -25°C to +55°C
  • -13°F to +131°F

IP Rating

IP20

Installation Type

Permanent installation, or
Temporary installation

Warranty Period

12 months

Downloads

Installation Manual

Power Meter - Panel Mount - Manual